Cat No: CCGS-LJX-0005 Datasheet
Product Name: Catalytic Combustion Combustible Gas Sensor, 0~100 %LEL
Quantities: - +
| Detailed Description | The catalytic element works based on the principle of catalytic combustion effect. It consists of two arms of a bridge composed of a detection element and a compensation element. When a flammable gas is encountered, the resistance of the detection element increases, and the output voltage of the bridge changes. This voltage change increases proportionally with the increase of gas concentration. The compensation element serves as a reference and provides temperature and humidity compensation. |
| Main Applications | It can be used for leak alarms or concentration detection of flammable gases such as natural gas, liquefied petroleum gas, and coal gas in households. |
| Product Type | Catalytic combustion gas sensor |
| Standard Package | Plastic packaging |
| Operating Voltage (V) | 3.0±0.1 |
| Operating Current (mA) | 110±10 |
| Sensitivity (mV) | 1% methane: 25~50 1% propane: 30~70 |
| Linearity | ≤5% |
| Measurement Range (%LEL) | 0~100 |
| Response Time (T90 ) | ≤10s |
| Recovery Time (T90 ) | ≤30s |
| Usage Environment | -40~+70℃, below 95%RH |
| Storage Environment | -20~+70℃, below 95%RH |
| Life | 5 years |
| Features | The bridge circuit output voltage is linear and has a fast response speed. It has good repeatability and selectivity. Resistant to H2S and interference from organosilicon. |
| Note | Actual product performance may vary depending on operating conditions, ambient temperature, and humidity. |
Eata Sensors is your strategic partner in precision sensing technology. We offer a full range of advanced sensor products, core components, and customized engineering services. We collaborate with global clients to jointly solve complex measurement challenges.